Nassguard supplies Tank Chime Sealing in Saudi with the Denso Viscotaq™ Tank Chime Sealing System, a flexible barrier that helps prevent water entering the interface between an aboveground steel tank and its concrete ring wall.
This exposed junction needs protection that follows the tank’s movement during filling and emptying. The Viscotaq tank chime seal combines conformable sealing materials with protective wrapping to maintain coverage around the tank-base perimeter.
Nassguard supplies project and maintenance requirements across Riyadh, Dammam, Jubail, Jeddah and Al Khobar.
The Denso Viscotaq Tank Chime Sealing System protects the external base area of aboveground steel storage tanks. It seals the junction where the projecting tank-bottom plate meets the supporting foundation.
Its visco-elastic material remains flexible and adhesive, helping the seal accommodate movement without forming a rigid bridge across the interface. The system uses ViscoSealant or a suitable ViscoMastic grade, combined with Viscotaq EZ Wrap and a compatible finish.
The system suits new and existing tanks and can accommodate future inspection and maintenance when the installation preserves the required access.
The system combines water exclusion with flexibility for the tank-to-foundation transition.
Tank base corrosion protection should address the full perimeter, including difficult transitions and previous repair areas.
For enquiries from Jeddah, Dammam, Jubail, Riyadh and Al Khobar, include photographs of the chime and foundation. A clear view of gaps, drainage and existing coatings helps define the work accurately.
A continuous seal needs sound surfaces, complete gap filling and properly finished edges.
Include the tank chime seal in routine external tank inspections.
A chime seal cannot restore corroded plate thickness, repair structural settlement or replace assessment of a leaking tank.
Nassguard supplies Denso Viscotaq tank chime sealing components for Saudi industrial projects and maintenance requirements. Detailed enquiries help establish a complete material package.
1. What does tank chime sealing protect?
It protects the external tank-base-to-foundation interface against water infiltration.
2. Can Viscotaq accommodate tank movement?
Yes, its visco-elastic materials remain flexible as the tank moves during normal filling and emptying.
3. Can the system cover an existing tank base?
Yes, following inspection, preparation and selection of an appropriate installation arrangement.
4. What are the main system components?
The system combines a suitable sealant or mastic, EZ Wrap and compatible topcoat, with adhesion promoter where specified.
5. Will it interfere with API 653 inspections?
Appropriate detailing preserves required inspection access, including visibility of relevant welds.
6. Does the seal repair tank-bottom corrosion?
No, it provides external protection; existing metal loss requires assessment and any necessary repair.
7. What should I send Nassguard for a quotation?
Provide tank dimensions, gap details, photographs, temperature, quantities and delivery location.
Tank Chime Sealing in Saudi with the Denso Viscotaq system helps protect a vulnerable junction around aboveground storage tanks. Its flexible materials maintain a protective transition between the steel base and concrete ring wall.
Reliable performance depends on preparation, compatible components and continued inspection. Contact Nassguard with your tank-base requirements for supply across Riyadh, Dammam, Jubail, Jeddah and Al Khobar.
| Item | System detail |
|---|---|
| System type | Visco-elastic tank chime sealing system |
| Main interface | Steel tank base to concrete ring wall |
| Sealing material | ViscoSealant, ViscoMastic or specified alternative |
| Higher-temperature mastic option | ViscoMastic XHT |
| Protective wrapping | Viscotaq EZ Wrap |
| Surface treatment | Viscotaq Adhesion Promoter, where specified |
| Compatible finish options | Archco 15 acrylic or Archco 65 polyurethane |
| Minimum steel preparation | St 2 / SSPC-SP 2 |
| Typical sealing depth | Approximately 25 mm into the gap |
| Minimum EZ Wrap strip overlap | 50 mm |
| Archco 15 temperature limit for this application | 65°C |
| Archco 65 temperature limit for this application | 93°C |